Free Cooling Using Winter’s Chill
by Engineering Staff, Motivair Corp.
September 1, 2007
An air-cooled chiller with integrated free cooling and
custom-designed PLC controls can help plants achieve year-round closed-loop
cooling at the lowest possible energy cost.
What
if you could turn off your chiller for three or four months out of the year
without compromising your year-round industrial process cooling operation? How
much energy would you save?
For plants located in regions that experience cold winter climates (below 41°F
[5°C]), using a chiller with a winter economizer system can substantially
reduce energy consumption. These chillers are designed to take advantage of
cold outside temperatures to provide “free cooling” for the manufacturing
process during the winter months. At the same time, the technology extends the
useful life of the chiller equipment by selectively reducing its operating
hours. With advanced integrated controls, these free-cooling chillers can help
plants achieve year-round cooling with the lowest possible energy and
maintenance costs.
A traditional approach to year-round cooling is an indoor, water-cooled
chiller, connected to an outdoor open-draft or closed-loop evaporative cooling
tower. Such systems typically have valves and crossover piping that allow the
chiller to be bypassed for winter operation. An open tower generally requires
an intermediate plate-and-frame heat exchanger to keep the airborne
contaminants entrained in the tower water from entering the process flow.
|
|
|
Physical locations north of a
theoretical east-west line from Norfolk, Va., to San Francisco, Calif., provide
the best ambient environment to optimize operation of integrated free-cooling
chillers for year-round cooling.
|
|
These
evaporative systems can save significant winter operating costs, but they have
some drawbacks due to their higher initial equipment, installation, maintenance
and power costs. All evaporative towers require makeup water equivalent to
approximately 2 gal/min/million BTU/hr for evaporative losses, plus sump
blowdown and drift losses. Water treatment is required for the makeup water. An
indoor water-cooled chiller also occupies potentially valuable floor space.
Finally, open towers cannot use glycols and have low temperature limitations to
avoid winter freezing problems.
Simply installing an outdoor air-cooled chiller with low ambient controls can
provide year-round cooling but creates an energy expense you would not have
with other methods. Additionally, the coldest winter days are the most
challenging operating conditions for air-cooled chillers.
In recent years, some of these year-round air-cooled chiller systems have been
retrofitted with remote glycol coolers (radiators) to pre-cool the return
chilled water in the winter months. While these units are a practical,
energy-saving addition, they occupy roof or ground space that could be used for
other purposes. Also, additional piping and insulation are required, along with
increased fan power for the fluid cooler. Control integration with the original
chiller requires careful consideration, especially when partial free-cooling is
both available and desirable in the moderately cool weather found during the
nighttime, spring and fall. Using partial free-cooling requires a motorized
valve, additional temperature controls and an advanced PLC to permit maximum
savings.
An Integrated Approach
Systems
with integrated free cooling and advanced PLC controls can provide complete
year-round closed loop cooling a low energy cost. The free-cooling coils
typically are fully integrated inside the chiller package, so extra floor space
for fans, pumps, valves, tanks or heat exchangers is not required, nor is
additional piping, electrical work, evaporative spray or makeup water needed.
These integrated free-cooling chillers are designed to produce 50 percent free
cooling at ambient temperatures approximately 10°F (6°C) below the design chilled
water temperature, or 100 percent free cooling at approximately 20°F (11°C)
below the chilled water supply temperature.
A major additional benefit of a free-cooling chiller is that the mechanical
refrigeration plant is not required to operate in the most difficult (winter)
environment. Head pressure control becomes increasingly difficult at low
ambient temperatures, and starting a refrigeration system in very low ambient
temperatures can be especially troublesome. Free cooling eliminates this
requirement for mechanical cooling in the winter, and therefore extends the
useful life of the mechanical system by reducing the number of operating hours
and eliminating the most difficult operating conditions.
Control. The free-cooling PLC determines when any free cooling can be achieved.
It continuously monitors the outside ambient temperature, the return chilled
water temperature, and the required chilled water supply temperature. The
controller automatically directs the return chilled water through the
economizer coils as soon as the ambient is cold enough to provide any useful
free cooling (figure 1).
|
|
|
Figure 1. The free-cooling PLC
continuously monitors the outside ambient temperature, the return chilled water
temperature, and the required chilled water supply temperature and
automatically directs the return chilled water through the economizer coils as
soon as the ambient is cold enough to provide any useful free cooling. |
|
The
refrigeration compressors run less frequently as the free-cooling effect
increases, until eventually they are no longer required and remain in standby
mode. At this time, full cooling capacity is provided by condenser fan power
alone. Variable-frequency drive control of the fans allows precise control of
the head pressure, maximizes energy savings and controls the chilled glycol
temperature at low ambient temperatures, when less airflow is required to
achieve 100 percent free cooling. All aspects of the mechanical and
free-cooling operation are controlled by the purpose-designed PLC, including
glycol-valve operation, fan-speed control and safety controls and alarms, in
addition to normal compressor and pump operation. On dual-circuit free-cooling
chillers, the PLC permits one circuit to operate in free-cooling mode (with the
compressor off and fans at full speed) while the other circuit operates
mechanically (with the compressor on and fan speed determined by head
pressure). In this way, maximum free-cooling savings can be achieved at any
ambient temperature.
The change from mechanical to partial or full free-cooling is transparent to
the operator and process. The LCD display indicates when the free-cooling
system is operational. The “smart” PLC control ensures the temperature does not
swing outside the design temperature control band. Similarly, when the system
switches out of free cooling, changes are not made to the chilled water
temperature control. At certain times of the year, the system might switch
compressors on and off several times during the day or night if the ambient is
hovering close to the free-cooling commencement temperature. The PLC prevents
short cycling of the free-cooling controls and compressors during any phase of
the operation. Compressor running hours are automatically logged by the PLC, so
the energy savings are available for inspection or verification at any time.
A Rapid Payback
|
|
| The free-cooling chiller
installed at AK Steel includes six scroll compressors in two independent
refrigeration circuits for maximum redundancy and reduced noise level. |
|
AK
Steel in Toledo, Ohio, needed a chiller for its new steel-tube production line.
The production line required year-round chilled water cooling for optimum
steel-tube production capacity. Specifically, the cooling process was quenching
the tubes at a controlled temperature of 70°F (21°C) immediately after the
forming operation to maintain the designed mechanical and metallurgical
tolerances. The Toledo area experiences approximately 500 hours at 50 to 55°F
(10 to 13°C) (25 percent free-cooling), 1,052 hours at 41 to 50°F (5 to 10°C)
(50 percent free-cooling) and 3,484 hours below 41°F (100 percent
free-cooling). With four 30-ton Motivair air-cooled chillers installed inside
the mill on an existing line, AK Steel felt confident about the brand and
wanted to take advantage of winter free-cooling opportunities for its new
production line.
In late 2006, the company installed a Motivair MLC-FC 330 free-cooling chiller.
The chiller was installed outside the building and supplies 60°F (16°C) chilled
glycol in a closed loop to the “cold side” of two plate-and-frame heat
exchangers in the plant. The “hot side” of the exchangers feeds water at 70°F
(21°C) in an open circuit to the large quenching tanks that process the
finished steel tubes.
The cooling load is approximately 122 tons, cooling 324 gal/min of 40 percent
glycol from 70 to 60°F (21 to 16°C) year-round. This application was especially
advantageous for a free-cooling chiller because the required chilled-water
supply temperature is relatively high and the Toledo area experiences a
relatively cool winter. As a result, more hours are available per year for
free-cooling operation, and compressor life is extended through reduced
operating hours.
The free-cooling chiller installed at AK Steel includes six scroll compressors
in two independent refrigeration circuits for maximum redundancy and reduced
noise level. Duplex pumps with auto-change and alarm functions ensure
continuous glycol circulation. The PLC monitors all chiller functions and
records compressor operating hours and the most recent 100 alarm conditions in
memory.
The total compressor power is 112 kW. At an average electrical cost of
$0.07/kWh, it was estimated that AK Steel will save approximately $32,412 per
year in energy costs compared to a standard air-cooled chiller without free
cooling for year-round cooling use. The payback period was calculated at less
than the first year for the capital cost of adding the free-cooling option to
the air-cooled chiller. In this advantageous application, the electrical energy
cost savings is sufficient to pay for the entire chiller and installation cost
in approximately five years.
The AK Steel example demonstrates that packaged air-cooled chillers with
integrated free-cooling can pay for the initial investment in a short amount of
time. The additional advantage of extended compressor life, achieved through
reduced run time, makes these chillers an attractive proposition to consider
for many year-round cooling applications. For free cooling to “make sense,” the
only requirements are an outside location for the packaged air-cooled chiller
with integrated free-cooling, and the addition of glycol as an antifreeze agent
to the cooling loop. Systems that incorporate the tank, pumps and controls in a
single outdoor, weatherproof package can minimize installation costs. Then only
connections to chilled glycol and electrical power are required.
The free-cooling savings can be calculated for an installation using ASHRAE
temperature bins, provided the design chilled-water temperature, installation
location and local electrical kW/h costs are known. Physical locations north of
a theoretical east-west line from Norfolk, Va., to San Francisco, Calif.,
provide the best ambient environment to optimize operation of integrated
free-cooling chillers for year-round cooling. In locations north of that
theoretical line, the typical average investment recovery period is 1 to 2 years,
depending on the geographic location and the chilled water temperature. Higher
chilled water temperatures and colder winter climates produce increased
savings.
|