Model LBW-420-LEL is designed for catastrophic leak detection and response before the situation gets to the lower explosion level (LEL). It displays ammonia concentration in percent from 0 to 9.9. It has a 4 to 20 mA analog output, scalable for 0 to 1 percent, 0 to 2 percent, or 0 to 10 percent. It has three latching relays capable of shutting down equipment. The detector connects to a control system, local alarms or exhaust fans. It also comes with an alarm disable mode to disarm alarms for testing, repair or calibration. It comes equipped with a long-life ammonia sensor that offers a quick, accurate response to ammonia concentrations. A fully isolated DC-to-DC power supply allows the detector to be powered from the same DC supply as the 4 to 20 mA monitoring circuits without concern for ground isolation.

Cool Air Inc.

763-205-0844

www.coolairinc.com